DISTRIBUTION CLASS DH · TS EN 60099-4
36 kV / 10 kA Silicone Polymer-Housed Metal-Oxide Surge Arrester
Protects distribution transformers, cable terminations and line equipment against lightning and switching overvoltages. Designed to TEDAŞ-MLZ/96-019.B with a gapless ZnO block column, HTV silicone housing and ground disconnector.
| Rated voltage, Ur | 36 kV |
| Continuous operating, Uc | ≥ 28,8 kV |
| Nominal discharge, In | 10 kA |
| Short-circuit, Is | 16 kA |
| High current impulse | 100 kA |
| Creepage | ≥ 1.116 mm |
STRUCTURE
Five components, one job: diverting overvoltage to earth
01
Top terminal and bird cap
Line terminal; the cap prevents phase-to-earth faults caused by birds and small animals.
02
HTV silicone rubber housing
Meets pollution level IV with ≥ 31 mm/kV creepage; hydrophobic, UV and ozone resistant.
03
Metal-oxide (ZnO) block column
Gapless series block stack. Block manufacturer, origin, count and dimensions are declared in the guaranteed particulars.
04
Ground disconnector
Disconnects the earth lead if the arrester fails; the network stays in service and the failed unit is visible.
05
Mounting bracket
Bracket for cross-arm or pole mounting; all steel fasteners are hot-dip galvanised.
TECHNICAL DATA
Electrical ratings and service conditions
ELECTRICAL CHARACTERISTICS
| Arrester class (TS EN 60099-4) | Distribution · DH |
| Highest system voltage, Um | 36 kV |
| Rated voltage, Ur | 36 kV |
| Continuous operating voltage, Uc | ≥ 28,8 kV |
| Nominal discharge current, In (8/20 µs) | 10 kA |
| High current impulse withstand (4/10 µs) | 100 kA |
| Repetitive charge transfer rating, Qrs | ≥ 0,4 C |
| Thermal charge transfer rating, Qth | ≥ 1,1 C |
| Rated short-circuit current, Is | 16 kA |
| Partial discharge (1.05 × Uc) | ≤ 10 pC |
HOUSING & DESIGN
| Housing material | HTV silicone rubber |
| Creepage | ≥ 1.116 mm · ≥ 31 mm/kV |
| Pollution level | IV · Very heavy |
| Block design | Gapless ZnO |
| Disconnector · bird cap | Yes · Yes |
SERVICE CONDITIONS · TEDAŞ
| Ambient temperature | −40 … +50 °C |
| 24-hour average | ≤ +35 °C |
| Altitude | ≤ 1000 m |
| Icing | Class 10 · 10 mm |
| Wind speed | ≤ 34 m/s |
| Relative humidity (24 h avg.) | ≤ %95 |
| Seismic acceleration | 0.5 g horizontal · 0.4 g vertical |
| Solar radiation | 1100 W/m² |
Residual voltages (steep current, lightning and switching impulses), the TOV curve and MOV block data are given in the datasheet and guaranteed particulars (TEDAŞ Annex-2).
TYPE TEST PROGRAMME
Complete, on the design to be delivered
Type tests per TEDAŞ-MLZ/96-019.B Table 9 and TS EN 60099-4 are performed on samples identical to the delivered design (same block count, length, creepage and insulation level) in a TS EN ISO/IEC 17025 accredited laboratory.
01
Housing insulation withstand
Lightning impulse and power-frequency withstand
02
Residual voltage
Steep current, lightning and switching impulses
03
Long-term stability
Accelerated ageing test
04
Repetitive charge transfer
Qrs ≥ 0.4 C verification
05
Heat dissipation and operating duty
Qth ≥ 1.1 C verification
06
Power-frequency TOV
Temporary overvoltage characteristic
07
Short circuit
Safe behaviour at 16 kA rated short-circuit current
08
Mechanical and sealing
Bending moment and moisture ingress tests
09
Polymer housing
TS EN 62217 and TS EN 60587 tests
10
Ground disconnector
Disconnector type tests
ROUTINE TESTS · EVERY UNIT
- Reference voltage
- Residual voltage
- Partial discharge
- Sealing check
SELECTION NOTE
The right ratings for 34.5 kV networks
Ur 36 kV and Uc ≥ 28.8 kV are selected to suit both resistance-earthed and solidly earthed systems. The lightning impulse residual voltage at 10 kA stays within TEDAŞ Table 8.b limits, well below the 170 kV peak insulation level of the protected equipment.
| System earthing | Resistance / solid |
| Protected equipment insulation level | 170 kV peak |
| Pollution level | III · IV |
DOCUMENT CENTRE
Datasheets, drawings and test files
The catalogue, datasheets, dimensioned drawings, type test reports and guaranteed particulars are shared on request per project or tender.
Product catalogue 2026
PDF · on request
K1 · K2 string insulator datasheet
PDF · on request
VHD-35 datasheet and dimensioned drawing
PDF · DWG · on request
36 kV / 10 kA surge arrester datasheet
PDF · on request
Guaranteed technical particulars (TEDAŞ Annex-2)
XLSX · on request
Type test reports
PDF · on request